Application of the Sinusoidal Voltage for Detection of the Resonance in Inductive Voltage Transformers
In the case of the inductive voltage transformer (VT), the resonance phenomenon may be the main reason for its poor transformation accuracy of the non-sinusoidal voltage. This problem mainly results from the leakage inductance and the parasitic capacitance of its primary winding. The application of...
Guardado en:
Autores principales: | , |
---|---|
Formato: | article |
Lenguaje: | EN |
Publicado: |
MDPI AG
2021
|
Materias: | |
Acceso en línea: | https://doaj.org/article/148cdca963a9432b9b44920e83c90e9a |
Etiquetas: |
Agregar Etiqueta
Sin Etiquetas, Sea el primero en etiquetar este registro!
|
id |
oai:doaj.org-article:148cdca963a9432b9b44920e83c90e9a |
---|---|
record_format |
dspace |
spelling |
oai:doaj.org-article:148cdca963a9432b9b44920e83c90e9a2021-11-11T15:51:36ZApplication of the Sinusoidal Voltage for Detection of the Resonance in Inductive Voltage Transformers10.3390/en142170471996-1073https://doaj.org/article/148cdca963a9432b9b44920e83c90e9a2021-10-01T00:00:00Zhttps://www.mdpi.com/1996-1073/14/21/7047https://doaj.org/toc/1996-1073In the case of the inductive voltage transformer (VT), the resonance phenomenon may be the main reason for its poor transformation accuracy of the non-sinusoidal voltage. This problem mainly results from the leakage inductance and the parasitic capacitance of its primary winding. The application of the sinusoidal voltage with a frequency from 20 Hz to 20 kHz presented in this study ensures proper identification of the resonance frequencies of the medium-voltage (MV) inductive VTs. The results are consistent with the values obtained in the reference condition at their nominal primary voltage. Therefore, it is proven that the proposed solution is effective in all cases. The influence of the main frequency variation of the non-sinusoidal primary voltage on the resonance properties of the inductive VT is also studied. Moreover, the tests indicate that the capacitance of the load of the secondary winding may cause a decrease in their resonance frequency.Michal KaczmarekErnest StanoMDPI AGarticleinductive voltage transformernon-sinusoidal medium voltagehigher harmonicsresonance for harmonicsinusoidal voltage of increased frequencyTechnologyTENEnergies, Vol 14, Iss 7047, p 7047 (2021) |
institution |
DOAJ |
collection |
DOAJ |
language |
EN |
topic |
inductive voltage transformer non-sinusoidal medium voltage higher harmonics resonance for harmonic sinusoidal voltage of increased frequency Technology T |
spellingShingle |
inductive voltage transformer non-sinusoidal medium voltage higher harmonics resonance for harmonic sinusoidal voltage of increased frequency Technology T Michal Kaczmarek Ernest Stano Application of the Sinusoidal Voltage for Detection of the Resonance in Inductive Voltage Transformers |
description |
In the case of the inductive voltage transformer (VT), the resonance phenomenon may be the main reason for its poor transformation accuracy of the non-sinusoidal voltage. This problem mainly results from the leakage inductance and the parasitic capacitance of its primary winding. The application of the sinusoidal voltage with a frequency from 20 Hz to 20 kHz presented in this study ensures proper identification of the resonance frequencies of the medium-voltage (MV) inductive VTs. The results are consistent with the values obtained in the reference condition at their nominal primary voltage. Therefore, it is proven that the proposed solution is effective in all cases. The influence of the main frequency variation of the non-sinusoidal primary voltage on the resonance properties of the inductive VT is also studied. Moreover, the tests indicate that the capacitance of the load of the secondary winding may cause a decrease in their resonance frequency. |
format |
article |
author |
Michal Kaczmarek Ernest Stano |
author_facet |
Michal Kaczmarek Ernest Stano |
author_sort |
Michal Kaczmarek |
title |
Application of the Sinusoidal Voltage for Detection of the Resonance in Inductive Voltage Transformers |
title_short |
Application of the Sinusoidal Voltage for Detection of the Resonance in Inductive Voltage Transformers |
title_full |
Application of the Sinusoidal Voltage for Detection of the Resonance in Inductive Voltage Transformers |
title_fullStr |
Application of the Sinusoidal Voltage for Detection of the Resonance in Inductive Voltage Transformers |
title_full_unstemmed |
Application of the Sinusoidal Voltage for Detection of the Resonance in Inductive Voltage Transformers |
title_sort |
application of the sinusoidal voltage for detection of the resonance in inductive voltage transformers |
publisher |
MDPI AG |
publishDate |
2021 |
url |
https://doaj.org/article/148cdca963a9432b9b44920e83c90e9a |
work_keys_str_mv |
AT michalkaczmarek applicationofthesinusoidalvoltagefordetectionoftheresonanceininductivevoltagetransformers AT erneststano applicationofthesinusoidalvoltagefordetectionoftheresonanceininductivevoltagetransformers |
_version_ |
1718433288679325696 |