Single-phase grounding fault line selection method based on zero-sequence current increment

To address single-phase grounding fault line selection problem in small current grounding distribution network, the paper proposes a fault line selection method based on zero-sequence current (ZSC) increment. The method downshift grounding transformer (GT) tap step-by-step to amplify fault current,...

Descripción completa

Guardado en:
Detalles Bibliográficos
Autor principal: Bai Hao
Formato: article
Lenguaje:EN
Publicado: Elsevier 2022
Materias:
Acceso en línea:https://doaj.org/article/25cdec254bb540bd8324a8bfe44cfdad
Etiquetas: Agregar Etiqueta
Sin Etiquetas, Sea el primero en etiquetar este registro!
Descripción
Sumario:To address single-phase grounding fault line selection problem in small current grounding distribution network, the paper proposes a fault line selection method based on zero-sequence current (ZSC) increment. The method downshift grounding transformer (GT) tap step-by-step to amplify fault current, defines the line with largest ZSC variation as fault line. The results of typical non-effectively grounding 10 kV distribution network show the rationality and applicability of the proposed method.