Optimal Control Method of Variable Air Volume Terminal Unit System

This study reviewed the existing studies on the types of variable air volume (VAV) terminal units, control and operation methods, prediction models, and sensor calibration methods. As a result of analyzing the existing research trends on the system type, characteristics, and control method of VAV te...

Descripción completa

Guardado en:
Detalles Bibliográficos
Autores principales: Hyo-Jun Kim, Young-Hum Cho
Formato: article
Lenguaje:EN
Publicado: MDPI AG 2021
Materias:
T
Acceso en línea:https://doaj.org/article/54e38e985fb446cfa4df523f7bae5222
Etiquetas: Agregar Etiqueta
Sin Etiquetas, Sea el primero en etiquetar este registro!
id oai:doaj.org-article:54e38e985fb446cfa4df523f7bae5222
record_format dspace
spelling oai:doaj.org-article:54e38e985fb446cfa4df523f7bae52222021-11-25T17:26:20ZOptimal Control Method of Variable Air Volume Terminal Unit System10.3390/en142275271996-1073https://doaj.org/article/54e38e985fb446cfa4df523f7bae52222021-11-01T00:00:00Zhttps://www.mdpi.com/1996-1073/14/22/7527https://doaj.org/toc/1996-1073This study reviewed the existing studies on the types of variable air volume (VAV) terminal units, control and operation methods, prediction models, and sensor calibration methods. As a result of analyzing the existing research trends on the system type, characteristics, and control method of VAV terminal units studies such as theoretical verification and energy simulation were conducted to improve the existing control methods, reset the set value using a mathematical model, and add a monitoring sensor for the application of control methods. The mathematical model used in the study of VAV terminal unit control methods was used to derive set values for minimum air volume, supply temperature, ventilation requirements, and indoor comfort. The mathematical model has a limitation in collecting input information for professional knowledge and model development, and development of a building environment prediction model using a black box model is being studied. The VAV terminal unit system uses a sensor to control the device, and when an error occurs in the sensor, indoor comfort problems and energy waste occur. To solve this problem, sensor calibration techniques have been developed using statistical models, mathematical models, and Bayesian statistical models. The possibility of developing a method for calibrating the variable air volume terminal unit sensor using the prediction model was confirmed. In conclusion, the VAV terminal unit system is one of the most energy efficient systems. The energy saving potential of current VAV systems can still be improved through control methods, the use of predictive models, and sensor calibration methods.Hyo-Jun KimYoung-Hum ChoMDPI AGarticlevariable air volume systemterminal unitoptimal controlprediction modelsensor calibrationTechnologyTENEnergies, Vol 14, Iss 7527, p 7527 (2021)
institution DOAJ
collection DOAJ
language EN
topic variable air volume system
terminal unit
optimal control
prediction model
sensor calibration
Technology
T
spellingShingle variable air volume system
terminal unit
optimal control
prediction model
sensor calibration
Technology
T
Hyo-Jun Kim
Young-Hum Cho
Optimal Control Method of Variable Air Volume Terminal Unit System
description This study reviewed the existing studies on the types of variable air volume (VAV) terminal units, control and operation methods, prediction models, and sensor calibration methods. As a result of analyzing the existing research trends on the system type, characteristics, and control method of VAV terminal units studies such as theoretical verification and energy simulation were conducted to improve the existing control methods, reset the set value using a mathematical model, and add a monitoring sensor for the application of control methods. The mathematical model used in the study of VAV terminal unit control methods was used to derive set values for minimum air volume, supply temperature, ventilation requirements, and indoor comfort. The mathematical model has a limitation in collecting input information for professional knowledge and model development, and development of a building environment prediction model using a black box model is being studied. The VAV terminal unit system uses a sensor to control the device, and when an error occurs in the sensor, indoor comfort problems and energy waste occur. To solve this problem, sensor calibration techniques have been developed using statistical models, mathematical models, and Bayesian statistical models. The possibility of developing a method for calibrating the variable air volume terminal unit sensor using the prediction model was confirmed. In conclusion, the VAV terminal unit system is one of the most energy efficient systems. The energy saving potential of current VAV systems can still be improved through control methods, the use of predictive models, and sensor calibration methods.
format article
author Hyo-Jun Kim
Young-Hum Cho
author_facet Hyo-Jun Kim
Young-Hum Cho
author_sort Hyo-Jun Kim
title Optimal Control Method of Variable Air Volume Terminal Unit System
title_short Optimal Control Method of Variable Air Volume Terminal Unit System
title_full Optimal Control Method of Variable Air Volume Terminal Unit System
title_fullStr Optimal Control Method of Variable Air Volume Terminal Unit System
title_full_unstemmed Optimal Control Method of Variable Air Volume Terminal Unit System
title_sort optimal control method of variable air volume terminal unit system
publisher MDPI AG
publishDate 2021
url https://doaj.org/article/54e38e985fb446cfa4df523f7bae5222
work_keys_str_mv AT hyojunkim optimalcontrolmethodofvariableairvolumeterminalunitsystem
AT younghumcho optimalcontrolmethodofvariableairvolumeterminalunitsystem
_version_ 1718412350012260352