Mathematical Modeling for the Clarifier Units and Turbidity Parameters in AL-KARAMA Treatment Plant

The high cost of chemical analysis of water has necessitated various researches into finding alternative method of determining portable water quality. This paper is aimed at modelling the turbidity value as a water quality parameter. Mathematical models for turbidity removal were developed based on...

Description complète

Enregistré dans:
Détails bibliographiques
Auteur principal: Hayder Mohammed Abdul-Hameed
Format: article
Langue:EN
Publié: Al-Khwarizmi College of Engineering – University of Baghdad 2005
Sujets:
pH
Accès en ligne:https://doaj.org/article/5d27277737f94f5c8177b1635a8c8df9
Tags: Ajouter un tag
Pas de tags, Soyez le premier à ajouter un tag!
Description
Résumé:The high cost of chemical analysis of water has necessitated various researches into finding alternative method of determining portable water quality. This paper is aimed at modelling the turbidity value as a water quality parameter. Mathematical models for turbidity removal were developed based on the relationships between water turbidity and other water criteria. Results showed that the turbidity of water is the cumulative effect of the individual parameters/factors affecting the system. A model equation for the evaluation and prediction of a clarifiers performance was developed:<br />Model: T = T0(-1.36729 + 0.037101&#8729;10&#955;pH + 0.048928t + 0.00741387&#8729;alk)<br />The developed model will aid the predictive assessment of water treatment plant performance. <br />The limitations of the models are as a result of insufficient variable considered during the conceptualization.<br />