RESULTS OF TESTS OF LIGHTNING-RODS WITH UNIVERSAL CLAMPS BY THE APERIODIC IMPULSES OF CURRENT OF ARTIFICIAL LIGHTNING WITH THE PEAK-TEMPORAL PARAMETERS RATIONED ON FOREIGN STANDARDS

Purpose. Test in obedience to the requirements of row of operating foreign standards of round metallic lightning-rods with the flat metallic universal clamps of the special type on firmness to direct action of аperiodic impulses of current of temporal form 10/350 μs by amplitude of 50 кА (N− class)...

Descripción completa

Guardado en:
Detalles Bibliográficos
Autores principales: M.I. Baranov, G.M. Koliushko, E.V. Kuzminskiy, Yu.I. Mysyuk, S.V. Rudakov
Formato: article
Lenguaje:EN
RU
UK
Publicado: National Technical University "Kharkiv Polytechnic Institute" 2015
Materias:
Acceso en línea:https://doaj.org/article/7bbb252da52a4126847df700228dcac6
Etiquetas: Agregar Etiqueta
Sin Etiquetas, Sea el primero en etiquetar este registro!
id oai:doaj.org-article:7bbb252da52a4126847df700228dcac6
record_format dspace
spelling oai:doaj.org-article:7bbb252da52a4126847df700228dcac62021-12-02T16:12:25ZRESULTS OF TESTS OF LIGHTNING-RODS WITH UNIVERSAL CLAMPS BY THE APERIODIC IMPULSES OF CURRENT OF ARTIFICIAL LIGHTNING WITH THE PEAK-TEMPORAL PARAMETERS RATIONED ON FOREIGN STANDARDS2074-272X2074-272Xhttps://doaj.org/article/7bbb252da52a4126847df700228dcac62015-06-01T00:00:00Zhttp://eie.khpi.edu.ua/article/view/44711/40947https://doaj.org/toc/2074-272Xhttps://doaj.org/toc/2074-272XPurpose. Test in obedience to the requirements of row of operating foreign standards of round metallic lightning-rods with the flat metallic universal clamps of the special type on firmness to direct action of аperiodic impulses of current of temporal form 10/350 μs by amplitude of 50 кА (N− class) and 100 кА (H− class). Methodology. The order of leadthrough of these tests is certain the followings normative documents: International IEC 62305-1: 2010, Russian national GOST R IEC 62305-1-2010 and German national DIN EN 50164-1:2008 Standards. Results. Conducted on a powerful high-voltage pulsed current of artificial linear lightning with the peak-temporal parameters and admittances of test rationed on the indicated foreign standards rationed that all of the lightning-rods tested in collection with universal clamps, isolating holders and ceramic elements of roof of technical building were survive electrodynamics and electrothermal action of in-use single short blow of an artificial storm digit. Originality. First in domestic practice the similar model tests of lightning-rods are conducted with universal clamps, executed from different explorer materials, on firmness to flowing to on by it the indicated large impulsive currents of artificial lightning. Practical value. Real firmness to lightning of round copper and zincked steel lightning-rods is certain with the flat copper, zincked steel and non-rusting steel universal clamps of the special execution.M.I. BaranovG.M. KoliushkoE.V. KuzminskiyYu.I. MysyukS.V. RudakovNational Technical University "Kharkiv Polytechnic Institute"articlemetallic lightning-rods with metallic universal clampsgenerator of aperiodic impulses of current of artificial lightningtest on firmness to lightningElectrical engineering. Electronics. Nuclear engineeringTK1-9971ENRUUKElectrical engineering & Electromechanics, Iss 3, Pp 48-54 (2015)
institution DOAJ
collection DOAJ
language EN
RU
UK
topic metallic lightning-rods with metallic universal clamps
generator of aperiodic impulses of current of artificial lightning
test on firmness to lightning
Electrical engineering. Electronics. Nuclear engineering
TK1-9971
spellingShingle metallic lightning-rods with metallic universal clamps
generator of aperiodic impulses of current of artificial lightning
test on firmness to lightning
Electrical engineering. Electronics. Nuclear engineering
TK1-9971
M.I. Baranov
G.M. Koliushko
E.V. Kuzminskiy
Yu.I. Mysyuk
S.V. Rudakov
RESULTS OF TESTS OF LIGHTNING-RODS WITH UNIVERSAL CLAMPS BY THE APERIODIC IMPULSES OF CURRENT OF ARTIFICIAL LIGHTNING WITH THE PEAK-TEMPORAL PARAMETERS RATIONED ON FOREIGN STANDARDS
description Purpose. Test in obedience to the requirements of row of operating foreign standards of round metallic lightning-rods with the flat metallic universal clamps of the special type on firmness to direct action of аperiodic impulses of current of temporal form 10/350 μs by amplitude of 50 кА (N− class) and 100 кА (H− class). Methodology. The order of leadthrough of these tests is certain the followings normative documents: International IEC 62305-1: 2010, Russian national GOST R IEC 62305-1-2010 and German national DIN EN 50164-1:2008 Standards. Results. Conducted on a powerful high-voltage pulsed current of artificial linear lightning with the peak-temporal parameters and admittances of test rationed on the indicated foreign standards rationed that all of the lightning-rods tested in collection with universal clamps, isolating holders and ceramic elements of roof of technical building were survive electrodynamics and electrothermal action of in-use single short blow of an artificial storm digit. Originality. First in domestic practice the similar model tests of lightning-rods are conducted with universal clamps, executed from different explorer materials, on firmness to flowing to on by it the indicated large impulsive currents of artificial lightning. Practical value. Real firmness to lightning of round copper and zincked steel lightning-rods is certain with the flat copper, zincked steel and non-rusting steel universal clamps of the special execution.
format article
author M.I. Baranov
G.M. Koliushko
E.V. Kuzminskiy
Yu.I. Mysyuk
S.V. Rudakov
author_facet M.I. Baranov
G.M. Koliushko
E.V. Kuzminskiy
Yu.I. Mysyuk
S.V. Rudakov
author_sort M.I. Baranov
title RESULTS OF TESTS OF LIGHTNING-RODS WITH UNIVERSAL CLAMPS BY THE APERIODIC IMPULSES OF CURRENT OF ARTIFICIAL LIGHTNING WITH THE PEAK-TEMPORAL PARAMETERS RATIONED ON FOREIGN STANDARDS
title_short RESULTS OF TESTS OF LIGHTNING-RODS WITH UNIVERSAL CLAMPS BY THE APERIODIC IMPULSES OF CURRENT OF ARTIFICIAL LIGHTNING WITH THE PEAK-TEMPORAL PARAMETERS RATIONED ON FOREIGN STANDARDS
title_full RESULTS OF TESTS OF LIGHTNING-RODS WITH UNIVERSAL CLAMPS BY THE APERIODIC IMPULSES OF CURRENT OF ARTIFICIAL LIGHTNING WITH THE PEAK-TEMPORAL PARAMETERS RATIONED ON FOREIGN STANDARDS
title_fullStr RESULTS OF TESTS OF LIGHTNING-RODS WITH UNIVERSAL CLAMPS BY THE APERIODIC IMPULSES OF CURRENT OF ARTIFICIAL LIGHTNING WITH THE PEAK-TEMPORAL PARAMETERS RATIONED ON FOREIGN STANDARDS
title_full_unstemmed RESULTS OF TESTS OF LIGHTNING-RODS WITH UNIVERSAL CLAMPS BY THE APERIODIC IMPULSES OF CURRENT OF ARTIFICIAL LIGHTNING WITH THE PEAK-TEMPORAL PARAMETERS RATIONED ON FOREIGN STANDARDS
title_sort results of tests of lightning-rods with universal clamps by the aperiodic impulses of current of artificial lightning with the peak-temporal parameters rationed on foreign standards
publisher National Technical University "Kharkiv Polytechnic Institute"
publishDate 2015
url https://doaj.org/article/7bbb252da52a4126847df700228dcac6
work_keys_str_mv AT mibaranov resultsoftestsoflightningrodswithuniversalclampsbytheaperiodicimpulsesofcurrentofartificiallightningwiththepeaktemporalparametersrationedonforeignstandards
AT gmkoliushko resultsoftestsoflightningrodswithuniversalclampsbytheaperiodicimpulsesofcurrentofartificiallightningwiththepeaktemporalparametersrationedonforeignstandards
AT evkuzminskiy resultsoftestsoflightningrodswithuniversalclampsbytheaperiodicimpulsesofcurrentofartificiallightningwiththepeaktemporalparametersrationedonforeignstandards
AT yuimysyuk resultsoftestsoflightningrodswithuniversalclampsbytheaperiodicimpulsesofcurrentofartificiallightningwiththepeaktemporalparametersrationedonforeignstandards
AT svrudakov resultsoftestsoflightningrodswithuniversalclampsbytheaperiodicimpulsesofcurrentofartificiallightningwiththepeaktemporalparametersrationedonforeignstandards
_version_ 1718384358269648896