General average model of T-type three-level converter for active compensation circuit of distribution network

The active compensation device, between the distribution network’s neutral point and the ground, compensates for the single-phase short-circuit current. And the T-type three-level circuit is a possible scheme for compensation devices. This paper proposes the T-type average model based on the above t...

Full description

Saved in:
Bibliographic Details
Main Authors: Hao Jin, Jianhua Wang, Jianfeng Zhao
Format: article
Language:EN
Published: Elsevier 2021
Subjects:
Online Access:https://doaj.org/article/8717a8eb82aa4218a8c268fb51eb1c6c
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:The active compensation device, between the distribution network’s neutral point and the ground, compensates for the single-phase short-circuit current. And the T-type three-level circuit is a possible scheme for compensation devices. This paper proposes the T-type average model based on the above topology, with a controlled voltage/current source, regardless of modulation or control methods. Compared with the two-level converter topology, the three-level converter topology improves the rated voltage stress, with few switching devices’ requirements. The modeling and simulation indicate that the T-type’s average model is identical to its switch model. And the T-type three-level converter can achieve the desired active compensation.