ASPECTS OF SURGE ARRESTERS’ MAXIMUM OPERATING VOLTAGE CHOICE FOR ELECTRICAL EQUIPMENT INSULATION PROTECTION IN 6-35 KV MAINS
The paper shows that, in 6-35 kV mains, application of a non-linear surge arrester (SA) with the maximum continuous admissible operating voltage which is 10% higher than the mains’ maximum operating voltage results in the SA protection from overheating and subsequent breakdown at nonnormable lifetim...
Saved in:
Main Author: | |
---|---|
Format: | article |
Language: | EN RU UK |
Published: |
National Technical University "Kharkiv Polytechnic Institute"
2013
|
Subjects: | |
Online Access: | https://doaj.org/article/972009d6ac0c453d99c2ad634c1f31a7 |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | The paper shows that, in 6-35 kV mains, application of a non-linear surge arrester (SA) with the maximum continuous admissible operating voltage which is 10% higher than the mains’ maximum operating voltage results in the SA protection from overheating and subsequent breakdown at nonnormable lifetime of single-phase arc faults. |
---|