DETERMINATION OF ANALYTICAL CALCULATION ERROR OF MAGNETIC FIELD OF HIGH-VOLTAGE CABLE LINES WITH TWO-POINT BONDED CABLE SHIELDS CAUSED BY NON-UNIFORM CURRENT DISTRIBUTION IN THE SHIELDS

This paper deals with the determination of analytical calculation error of magnetic field of high-voltage cable lines in two-point bonded cable shields caused by non-uniformity of the current distribution in the shields. The relative error is determined by comparing numerical calculation of magnetic...

Descripción completa

Guardado en:
Detalles Bibliográficos
Autor principal: A. O. Tkachenko
Formato: article
Lenguaje:EN
RU
UK
Publicado: National Technical University "Kharkiv Polytechnic Institute" 2017
Materias:
Acceso en línea:https://doaj.org/article/a7b8ae6229964d24ad9a9b7f5de119ef
Etiquetas: Agregar Etiqueta
Sin Etiquetas, Sea el primero en etiquetar este registro!
Descripción
Sumario:This paper deals with the determination of analytical calculation error of magnetic field of high-voltage cable lines in two-point bonded cable shields caused by non-uniformity of the current distribution in the shields. The relative error is determined by comparing numerical calculation of magnetic field obtained in the COMSOL Multiphysics software with the analytical one. It is shown that the maximum value of relative error does not exceed 8 %. The obtained error values are verified by testing the numerical calculation and confirmed by results of experiment. In paper proves the correctness of the analytical calculation of magnetic field of cable lines at the points of its normalization, which is carried out without taking into account the non-uniform current distribution in the cable shields.