Research on electric potentials alignment on the ground surface within the grounding conductor territory
Results of research on distribution of electric potentials on the earth surface in the territory with a grounding conductor are analyzed. It is shown that potential over the center of a square grounding conductor can be higher than that over the electrode. It is suggested to estimate the limit size...
Guardado en:
Autores principales: | , , |
---|---|
Formato: | article |
Lenguaje: | EN RU UK |
Publicado: |
National Technical University "Kharkiv Polytechnic Institute"
2014
|
Materias: | |
Acceso en línea: | https://doaj.org/article/aa3a1c4f99c247b2a62f7249bd834d7c |
Etiquetas: |
Agregar Etiqueta
Sin Etiquetas, Sea el primero en etiquetar este registro!
|
Sumario: | Results of research on distribution of electric potentials on the earth surface in the territory with a grounding conductor are analyzed. It is shown that potential over the center of a square grounding conductor can be higher than that over the electrode. It is suggested to estimate the limit size of the cell of a complex net grounding conductor depending on the depth of its laying. It is found that a two-level design of the grounding conductor reduces touch voltage. Novelty of the results consists in application of a mathematical model to investigating electric characteristics of a two-level grounding conductor versus its laying depth. |
---|