An overview of methods for eliminating the effects of interference in an active high-voltage power facility

In this paper, practical and conceptual problems related to the way of suppressing or eliminating the influence of interference (at a frequency of 50 Hz) in an active high-voltage power facility are discussed. The problem is relevant in the context of measuring the safety characteristics of the grou...

Descripción completa

Guardado en:
Detalles Bibliográficos
Autor principal: Kostić Vojin I.
Formato: article
Lenguaje:EN
SR
Publicado: Savez inženjera i tehničara Srbije 2021
Materias:
Acceso en línea:https://doaj.org/article/bbcf679410764d0489100d320820c1f4
Etiquetas: Agregar Etiqueta
Sin Etiquetas, Sea el primero en etiquetar este registro!
Descripción
Sumario:In this paper, practical and conceptual problems related to the way of suppressing or eliminating the influence of interference (at a frequency of 50 Hz) in an active high-voltage power facility are discussed. The problem is relevant in the context of measuring the safety characteristics of the grounding system: grounding system impedance, touch voltage and step voltage. The paper gives an evolutionary overview of title methods. The review focuses on the characteristic problems and shortcomings of individual methods. Also, the basic characteristics of the author's FSM (Frequency Shift Method) method, which guarantees precise control of interference, are elaborated. In this sense, the FSM method is the basis for accurate and economical measurement of the safety characteristics of the grounding system.