Normalization of double-circuit overhead line magnetic field inside Khrushchev building

This paper deals with the mitigation of 110 kV double-circuit overhead line magnetic field inside five-story Khrushchev buildings. We show that the magnetic field can exceed the reference level 0.5 μT in 90 % part of living space. To mitigate the magnetic field, we propose the inverted L-shaped grid...

Descripción completa

Guardado en:
Detalles Bibliográficos
Autores principales: K. V. Chunikhin, V. S. Grinchenko
Formato: article
Lenguaje:EN
RU
UK
Publicado: National Technical University "Kharkiv Polytechnic Institute" 2021
Materias:
Acceso en línea:https://doaj.org/article/da72f93221f949a1902c6615eb3e1e81
Etiquetas: Agregar Etiqueta
Sin Etiquetas, Sea el primero en etiquetar este registro!
Descripción
Sumario:This paper deals with the mitigation of 110 kV double-circuit overhead line magnetic field inside five-story Khrushchev buildings. We show that the magnetic field can exceed the reference level 0.5 μT in 90 % part of living space. To mitigate the magnetic field, we propose the inverted L-shaped grid shield with conductors on the wall and in the attic of the building. Using the analytical model of the grid shield and the numerical simulation, we determine the parameters of the L-shaped grid shield which provides the magnetic field normalization in 97 % part of living space. Further improvement of the grid shield profile, in particular, the placement of some conductors in the basement, allows to reduce the quantity of metal of the shield by 15 % while maintaining the shielding efficiency. Also we consider the magnetic field normalization for the overhead line with a rated current of 500 A. In this case, the quantity of metal of the grid shield increases 2.74 times.