Study on The Effect of Different Plenum Chamber Coefficients on Frosting of Air-cooler

The performance of the air-cooler in the refrigeration system plays a key role in improving the energy efficiency. Here, the plenum chamber coefficient was defined to study a possible way of enhancing the refrigeration system performance. In order to investigate the influence of the plenum chamber c...

Descripción completa

Guardado en:
Detalles Bibliográficos
Autores principales: Liu Bin, Shi Shengqiang, Liu Yongshan, Bennacer Rachid, Chen Aiqiang, Theodorakis Panagiotis E.
Formato: article
Lenguaje:EN
FR
Publicado: EDP Sciences 2021
Materias:
Acceso en línea:https://doaj.org/article/f7f36af31edd4b04af2bf7e43348ab94
Etiquetas: Agregar Etiqueta
Sin Etiquetas, Sea el primero en etiquetar este registro!
Descripción
Sumario:The performance of the air-cooler in the refrigeration system plays a key role in improving the energy efficiency. Here, the plenum chamber coefficient was defined to study a possible way of enhancing the refrigeration system performance. In order to investigate the influence of the plenum chamber coefficient on the frosting and the cooling system of the chillers, three plenum chamber coefficients (0.74,0.97,1.2) were studied under high humidity. The temperature decreasing curve of the environmental chamber, the velocity distribution of the air cooler, and the frost accumulation under and on the air-cooler were analysed. The results show that the frost accumulation on the tube will increase with the increase of the plenum chamber coefficient and the frost accumulation on the fin will increase at first and then decrease with the increase of the plenum chamber coefficient. On the whole, in this study, frosting is the most obvious when the plenum chamber coefficient was 0.97