ANALYSIS OF PRESSURE LOSS COMPONENTS IN AN INDUSTRIAL EXTRACT DUCT SYSTEM
The frictional head loss and the loss through fittings are computed for branch duct runs of an industrial extract ventilation system. Results show increases of both of the aforementioned loss components with increase in duct length. Furthermore, the fraction of the total loss due to fittings decrea...
Enregistré dans:
Auteur principal: | |
---|---|
Format: | article |
Langue: | EN |
Publié: |
Alma Mater Publishing House "Vasile Alecsandri" University of Bacau
2016
|
Sujets: | |
Accès en ligne: | https://doaj.org/article/97f3efbf842441ce91c039db5c36657c |
Tags: |
Ajouter un tag
Pas de tags, Soyez le premier à ajouter un tag!
|
Résumé: | The frictional head loss and the loss through fittings are computed for branch duct runs of an industrial extract ventilation system. Results show increases of both of the aforementioned loss components with increase in duct length. Furthermore, the fraction of the total loss due to fittings decreases from 0.60 to 0.45, with a corresponding increase of the fraction due to friction (from 0.40 to 0.55).Representative fractions of head loss components, obtained in the manner of this study, are shown to facilitate loss estimates and extract fan selection.
|
---|